H07RN-F vs H05RN-F: Choosing Rubber Flexible Cable by Voltage, Sheath and Drum Test Data

What the designation letters mean under EN 50525-2-21, why class 5 conductor resistance is the fastest check on a downgrade, what HAR marking does and does not prove, drum lengths, and the per-reel certificate fields to demand.

By VeraBOM & B2B Partner engineering & export team9 min read
H07RN-F vs H05RN-F: Choosing Rubber Flexible Cable by Voltage, Sheath and Drum Test Data — illustration

Read the designation before you read the price

H means harmonised, built to the EN 50525 series. The next two digits are the voltage class: 05 is 300/500 V, 07 is 450/750 V. The letters after that describe the materials: R is rubber insulation, N is a polychloroprene sheath, and F is a flexible class 5 conductor. So H07RN-F is a 450/750 V cable with rubber insulation, polychloroprene sheath and flexible stranded copper.

EN 50525-2-21 covers four related constructions: H05RR-F, H05RN-F, H07RR-F and H07RN-F. The RR types use ordinary rubber compounds and are not oil resistant; the RN types use crosslinked EPR insulation and crosslinked polychloroprene sheath, which is what buys the oil, ozone and weather resistance. Substituting an RR cable for an RN cable is the classic downgrade, and the printed legend is the only thing that reveals it.

Note what the letters do not cover. Temperature class is not in the designation, the reaction-to-fire class lives under EN 50575, and neither H05RN-F nor H07RN-F is a welding lead — that is H01N-D under EN 50525-2-81, built for 100 V and spark resistance. A submersible pump needs the water-resistant H07RN8-F variant, and a 180 °C appliance lead needs silicone.

300/500 V against 450/750 V: what the difference is worth

The U0/U marking is phase-to-earth over phase-to-phase voltage the insulation is designed for, and it drives the routine test voltage, the minimum insulation thickness and the clearance the cable is allowed to work at. A 300/500 V cable is rated for internal wiring, appliance connections and portable equipment on standard single-phase supplies. A 450/750 V cable covers three-phase 400 V systems, site distribution, generators, hoists and festoon runs.

Mechanically the two are near-identical in small sizes; the difference shows up in wall thickness, outer diameter and the test regime. H05RN-F is the right answer inside a panel or an appliance where the cable is protected. H07RN-F is the right answer anywhere the cable is handled, dragged, run outdoors, or connected to a 400 V supply — including a temporary site supply, where a 2.5 mm² H07RN-F lead is the normal minimum through a 110 V site transformer and the cable is still specified at the higher class for mechanical duty.

The UK equivalent is BS 7919, and most importers simply accept H07RN-F as the harmonised construction. Where a tender names BS 7919 and the offer says EN 50525-2-21, that is normally acceptable; where the offer says "rubber flexible cable to international standard", ask which standard, which clause and which test report, before the container is booked.

Class 5 conductor and the resistance table that catches a short measure

The F in the designation means a class 5 flexible stranded copper conductor to EN 60228. Class 5 sets both a maximum strand diameter — 0.26 mm for 1.5 mm² up to about 0.51 mm for 25 mm² — and a maximum DC resistance at 20 °C that every genuine cable must beat: 13.3 Ω/km for 1.5 mm², 7.98 for 2.5 mm², 4.95 for 4 mm², 3.30 for 6 mm², 1.91 for 10 mm², 1.21 for 16 mm² and 0.780 for 25 mm².

That table is the cheapest quality control available to a buyer, because it cannot be faked without changing the copper. Measure resistance on a sample length with a four-wire micro-ohmmeter, correct to 20 °C, and compare. A reading above the limit means less copper than declared: an undersized cross-section, a higher-resistance alloy, or copper-clad aluminium. CCA also weighs noticeably less — for 3G2.5 the pure copper content is about 67 kg/km, and the finished cable weighs roughly 200 kg/km; for 3G1.5 those figures are about 40 kg/km and 150 kg/km.

Check the current-carrying capacity separately, from the installation method table in IEC 60364-5-52 rather than from a datasheet, because RN cable is rated at a 60 °C conductor and derates harder in conduit, in bundles or at high ambient than a 90 °C XLPE cable. Voltage drop is the other silent failure: 2.5 mm² carrying 16 A over a 50 m run drops about 12.8 V, which is 5.6% of a 230 V supply and outside the usual 3-5% guidance.

Temperature, oil, ozone and UV

RN cable is rated for a maximum conductor temperature of 60 °C in normal service, with a short-circuit limit of 200 °C for five seconds, and an installation and ambient range of roughly −25 °C to +60 °C fixed, and about −15 °C for flexible movement. Below that the polychloroprene stiffens and cracks on bending — a real issue for winter site work and cold-store duty, where a special low-temperature compound has to be specified explicitly.

Oil resistance comes from the EM2 sheath and is proven by immersion in a reference mineral oil at elevated temperature under the EN 60811 test methods, with limits on tensile strength change, elongation change and volume swell. Ozone resistance and the hot-set test — which proves the compound is genuinely crosslinked rather than thermoplastic — come from the same series. Ask for the type-test report by clause, not for the sentence "oil resistant".

Weathering is where cheap cable separates. Polychloroprene is inherently UV and ozone tolerant, which is why H07RN-F is used outdoors on generators, irrigation pumps, stage equipment and agricultural machinery. A sheath loaded with excess filler to displace rubber loses that: it goes chalky, whitens on bending and cracks within a season. The tell before installation is a dull, powdery surface and white stress marks where the cable is flexed by hand.

HAR marking, CE marking and what each proves

The HAR mark is third-party certification under the European harmonisation agreement: a national certification body audits the factory, tests the product and keeps production under continuous surveillance. A cable printed with H07RN-F and the HAR mark has been built under that surveillance; a cable printed only with H07RN-F may still be a correct EN 50525-2-21 construction, but the conformity is self-declared. Where a tender asks for HAR, the certificate number and issuing body should be on the invoice and the packing list.

CE marking and HAR marking are different things. Under the Low Voltage Directive 2014/35/EU the cable is in scope, and where it is permanently installed in a construction work the Construction Products Regulation route applies through EN 50575: CE marking, a declaration of performance with a reaction-to-fire Euroclass from Aca to Fca (H07RN-F typically lands at Eca or Fca), factory production control and an AVCP system with a notified body number. Portable and flexible cords that are not permanently installed fall outside EN 50575 scope, which is exactly why a DoP cannot be produced for a drum of extension leads.

The printed legend on the sheath should therefore carry, at minimum: the HAR mark where claimed, the designation H07RN-F or H05RN-F, the size such as 3G2.5, the standard reference, the manufacturer identification, the year of manufacture, and continuous metre marking. Core colours follow the harmonised HD 308 code — for a 3G cable, brown, blue and green/yellow — and non-harmonised colours on a supposedly EN-built cable are a strong hint that the construction is not either.

Drum lengths, reel numbers and the per-reel certificate

Standard export packing is 100 m on cardboard drums for small sizes, 500 m or 1,000 m on wooden drums for 1.5 mm² to 35 mm², and cut lengths coiled at 25, 50 or 100 m for retail or spares. State the length and the tolerance on the order and prefer no negative tolerance; a metre-marked sheath lets you verify the count at the dock without unreeving anything.

Every reel needs its own number, printed on the flange and repeated on the test certificate, the packing list and the drum label. Reel dimensions, tare, gross and net weight belong on the packing list too, because a wooden drum is a handling and a lashing decision at the destination, not only at loading.

A usable per-reel certificate carries measured values, not a product description: reel number and length, size and construction, standard and clause, measured conductor resistance at 20 °C corrected, the routine voltage withstand test result, measured insulation and sheath thickness against nominal and minimum, measured mean outer diameter against the published band, production date, batch or melt reference for the copper rod, and the inspector signature. Minimum thickness rules to check against: insulation must be at least 90% of nominal minus 0.1 mm at any point, and sheath at least 85% of nominal minus 0.1 mm, per EN 50525-1.

Downgrade and counterfeit tells

Start with the legend. Ink that wipes off with a thumb or a solvent-soaked cloth, a designation printed on a construction whose insulation thickness does not support it, a missing HAR mark where HAR was ordered, a drum label that does not match the sheath print, and a certificate that covers the whole order in one block with no per-reel values are all disqualifying on their own.

Then the physical checks that take ten minutes: measure the overall diameter with a caliper against the band published in EN 50525-2-21 (a mean diameter below the lower limit means shaved insulation); measure insulation and sheath thickness on a cut section; count the strands and measure strand diameter against the class 5 limits; weigh a one-metre cut length and compare against the nominal mass per kilometre; and flex the cable sharply by hand looking for white stress marks in the sheath.

Finally the electrical ones: conductor resistance corrected to 20 °C against the EN 60228 table, and a 2.5 kV withstand test on the cores per the routine test requirements of EN 50525-1. Where a shipment is large or the destination authority samples it, take two witness samples from different reels and send them to an accredited laboratory before the goods are committed. The cost of that test is a rounding error against a rejected container and a recall of cable already installed in the field.

Questions this guide raises

Can H05RN-F be used instead of H07RN-F?

Only inside equipment and on circuits up to 300/500 V where the cable is protected from handling and weather. For three-phase 400 V supplies, site distribution, generators, hoists and any outdoor or dragged application, specify H07RN-F. The materials are similar; the voltage class, insulation thickness and test regime are not.

Does HAR marking mean the cable is CE marked?

They are separate marks. HAR is third-party certification under the harmonisation agreement with continuous factory surveillance. CE relates to the Low Voltage Directive and, for cables permanently installed in construction works, to EN 50575 with a declared reaction-to-fire class and a declaration of performance. Ask for both references where your market needs them.

What is the fastest way to detect copper-clad aluminium sold as copper?

Weigh a metre cut length and compare against the nominal mass per kilometre, then measure conductor resistance and correct to 20 °C against the EN 60228 class 5 table. CCA is lighter and has roughly 1.6 times the resistance of the same copper cross-section. Cutting a strand also shows a silver core under a copper-coloured surface.

What drum lengths and markings can be supplied?

Standard export packing is 100 m cardboard drums, 500 m and 1,000 m wooden drums, plus coiled cut lengths of 25, 50 and 100 m. Custom lengths and a custom printed legend are normal orders; a custom legend typically needs a minimum run per size once the print plate is set. Every reel is numbered and carries its own test certificate.

Written first reply within 1 working day; priced answer within 2-5 working days.